Switch Amplifier KFA6-SR2-Ex1.W.LB

KFA6-SR2-Ex1.W.LB
  • 1-channel isolated barrier
  • 230 V AC supply
  • Dry contact or NAMUR inputs
  • Relay contact output
  • Fault relay contact output
  • Line fault detection (LFD)
  • Reversible mode of operation
  • Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Dane techniczne  KFA6-SR2-Ex1.W.LB

General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Connectionterminals 14, 15
Rated voltage207 ... 253 V AC, 45 ... 65 Hz
Power dissipation1.2 W
Power consumptionmax. 1.3 W
Input
Connection sidefield side
Connectionterminals 1+, 2+, 3-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Output
Connection sidecontrol side
Connectionoutput I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Output Isignal ; relay
Output IIsignal or fault message ; relay
Contact loading253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Mechanical life107 switching cycles
Transfer characteristics
Switching frequency≤ 10 Hz
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
InputEN 60947-5-6:2000
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificatePTB 00 ATEX 2081
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
InputEx ia
Voltage10.6 V
Current19.1 mA
Power51 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
Output
Contact loading253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.)
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012
International approvals
FM approval
Control drawing116-0035
UL approval
Control drawing116-0145
CSA approval
Control drawing116-0047
IECEx approval
IECEx certificateIECEx PTB 11.0031
IECEx marking[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFA6-SR2-Ex1.W.LB

This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area.

The proximity sensor or switch controls a form C changeover relay contact for the safe area load. The normal output state can be reversed using switch S1. Switch S2 allows output II to be switched between a signal output or an error message output. Switch S3 is used to enable or disable line fault detection of the field circuit.

During an error condition, relays revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44.

Datasheet: KFA6-SR2-Ex1.W.LB

DatasheetTyp plikuRozmiar pliku
Datasheet KFA6-SR2-Ex1.W.LBPDF1268 KB
Fiche de données KFA6-SR2-Ex1.W.LBPDF1276 KB
Datenblatt KFA6-SR2-Ex1.W.LBPDF1268 KB
Datasheet KFA6-SR2-Ex1.W.LBPDF1328 KB
Hoja de datos KFA6-SR2-Ex1.W.LBPDF1280 KB

Documents: KFA6-SR2-Ex1.W.LB

ManualsTyp plikuRozmiar pliku
ManualPDF3685 KB
HandbuchPDF3693 KB
Instruction manuals
ИнструкцииPDF172 KB
Instruction manual / BetriebsanleitungPDF334 KB
Návod k poużitíPDF168 KB
Instruktions manualPDF167 KB
Instruction manualPDF176 KB
KasutusjuhendPDF163 KB
KäyttöohjePDF163 KB
Manuel d'instructionsPDF169 KB
BetriebsanleitungPDF177 KB
Οδηγίες χρήσηςPDF175 KB
HandleidingPDF168 KB
Instruction manual / BetriebsanleitungPDF166 KB
Használati útmutatóPDF168 KB
Manuale di istruzioniPDF167 KB
Lietošanas pamācībaPDF167 KB
Instrukciju vadovasPDF168 KB
Instrukcja obsługiPDF168 KB
Manual de instruçõesPDF168 KB
Manual de utilizarePDF168 KB
Návod na poużitiePDF168 KB
Navodila za uporaboPDF165 KB
Manual de instruccionesPDF169 KB
ManualPDF164 KB
Application reports
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StagePDF566 KB
Application Report - Energy Generation in Wastwater Treatment PlantsPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StagePDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsPDF526 KB
Applikationsbericht - Biologische Abwasserreinigung und NachklärungPDF568 KB
Applikationsbericht - Energiegewinnung in KläranlagenPDF535 KB
Applikationsbericht - Rechenanlagen in KläranlagenPDF578 KB
Applikationsbericht - Sandfang und VorklärungPDF434 KB
Applikationsbericht - Sicherer Brennstofftransport in KohlekraftwerkenPDF393 KB
Applikationsbericht - Stromerzeugung in KohlekraftwerkenPDF416 KB
Applikationsbericht - Wasserzulauf in KläranlagenPDF527 KB
Documents
Safety ManualPDF450 KB
Safety ManualPDF580 KB

CAD+CAE: KFA6-SR2-Ex1.W.LB

CADTyp plikuRozmiar pliku
CAD 3-D / CAD 3-DSTP3123 KB
CAD Portal / CAD PortalLINK---
EPLAN
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZEDZ1375 KB

Produkty powiązane: KFA6-SR2-Ex1.W.LB

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
1-channel, Dry contact input, For line fault detection (LFD)pa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.